PARAM

 

param

General Information :

 

Air insulated switchgear panels (AIS), with Megawin Electric make fixed type vacuum circuit breakers (VCB) with Magnetic Actuator Mechanism. The panels and breakers are designed, type tested & complying to latest IEC standards & GCC specifications

 Applicable standards

Complies with IS/IEC 62271-1, 100, 200

 

Product Features
  • Very compact. Low civil cost. User friendly
  • Separate compartments, with metallic partition, for busbar, cable, circuit breaker, low voltage and VT as applicable
  • Eco friendly as arc interruption happened in vacuum and SF6 free
  • Fixed VCB with magnetic actuator mechanism
  • Magnetic actuator mechanism has endurance of 100,000 mechanical operations
  • Provided with all mandatory safety interlocks and padlocks
  • Ready to connect to any remote control & monitoring system and to any SCADA system
  • Sufficient head room in the cable compartment i.e, more than 650mm, for the connection & bending radius of power cables
  • Suitable for single or three core cables, with a maximum of 12 per phase
  • Busbar and cable compartments have tool based access
  • Busbars are made of electrolytic copper
  • Busbar compartment is segregated for each panel for not letting any arc fault to adjacent panels
  • Complete with CTs, PTs, Relays, Meters, Control & Indication devices fully wired up and ready to use

 

Application
  • Transformer Switching
  • Capacitor Bank Switching
  • Motor Switching
  • Feeder Switching
  • Furnace Switching

 

  KEY TECHNICAL DATA  
Parameter  Unit Rating
 Rated Voltage  kV  12
 Rated Current  Amps  1250
 Rated busbar continuous Current  Amps  1250
 Short time current rating  kA/sec  31.5 / 3 sec
 Rated Short circuit breaking current  kA(rms)  31.5
 Rated making current  kA(peak)  78.75
 Rated cable charging current  Amps  25 (CC2)
 Rated capacitor breaking current  Amps  400 (C2)
 Rated insulation level ( B.I.L.)  kV  12 / 35 / 95
 Width x Depth x Height  Mm  500x1200x2490
 Weight of completed Breaker Panel  Kgs.  800
 Degree of ingress Protection  IP Class  Indoor IP4X / Outdoor IP 55
 Category of switchgear  As per IEC  E2, C2, M2
 Internal Arc tested for  AFLR  31.5kA / 1 second

 

 

 

 

Download Attachment